SA contactors

Contactors series for the current ranging from 125 A to 550 A and voltage up to 1000 V

Construction
SA contactors consist of:
– three-pole, double-break main circuit contact system,
– extinguishing chamber equipped with a contactor status indicator located in the central hole,
– two units of the auxiliary circuits,
– alternative current electromagnet drive.

SA contactors can be equipped with a mutual mechanical interlocking system (independent of electrical interlocking). Extinguishing chambers, electromagnet drive coils, moving and fixed contacts of main circuits can be easily removed and exchanged. Spare parts list is attached to the service manual provided together with a contactor.

Application
Main application of the SA contactors is remote switching of threephase alternative current circuits in conditions specified by utilization category AC3 and AC4 (switching of squirrel-cage motors). Switching of slipring motors (category AC2) or heating devices (category AC1) is also possible. Ambient temperature shall not exceed +55 °C and shall not be lower than -25 °C near to contactor without enclosure. Operating conditions in non-typical applications shall be agreed with manufacturer. SA contactors are designed for indoor use in wide range of climatic conditions at the altitude up to 2000 m a.s.l. and shall be installed on stiff, vertical supporting structures not exposed to heavy vibrations or shocks. Contactor’s current paths shall be guided vertically. SA contactors fulfil requirements of PN-EN 60947-4-1standard.



Product range

Contactor type
Identifcation No
Item No.
-
A
B
C
-
D
SA55M
B251
T 0 601-T08...
SA75M
B261
T
0 601-T07...
SA90M
B271
T 0 601-T06...
SA110M
B281
T
0 601-T05...
SA132
B291
T 601-T04...
SA160
B301
T 601-T03...
SA200
B321
T 601-T02...
SA250
B341
T 601-T01...


A – auxiliary contacts (see diagrams)
| 1 |
Basic version: standard internal switches
| 2 | Special version: standard internal and external switches
| 3 | Special version 1): standard internal switches, early or late make external switches

1) Special version in development SA..M contactors are manufactured in an universal design.


B - Auxiliary contacts number
| 2 | 2 |
2z+2r
| 2 | 4 |
2z+4r
| 3 | 3 |
3z+3r
| 4 | 2 |
4z+2r
| 4 | 8 |
4z+8r
| 6 | 6 |
6z+6r
| 8 | 4 |
8z+4r
| 4 | 8 |
4z+8r
| 6 | 6 |
6z+6r
| 8 | 4 |
8z+4r

C – Coil voltage (50Hz)
| 2 | 42 V
| 4 | 110 V
| 3 | 230 V
| 5 | 400 V
| 8 | 500 V
| 9 | Other – on request

D – Climatic area design
| 1 | temperate climate
| 4 | tropical climate
| 6 |  maritime climate


Ordering example

SA110 M contactor, rated continuous current up to 220 A, with auxiliary contacts (4NC+2NO), with a coil rating 230 V 50 Hz: SA200 CONTACTOR 230 V 50 Hz B281 1423T0


Technical data

Main contacts
SA55M
SA75M
SA90M
SA110M
SA132
SA160
SA200
SA250
Rated insulation voltage Ui
[V]
1000
Rated continous current Iu
40 ºC
[A]
125
180
200
220
250
300
400
550
Rated swit. current U AC1
55 ºC
[A]
125
160
180
200
230
280
380
530
Rated power of squirel-cage motors at utuilzation category
AC2 / AC3
230 V
[kW]
35
45
55
65
75
90
125
150
400 V
55
75
90
110
132
160
200
250
500 V
75
90
110
145
160
200
250
330
690 V
90
110
132
132
200
250
315
375
AC4
230 V
[kW]
25
30
37
45
50
55
60
65
400 V
30
37
45
75
85
95
110
145
500 V
45
45
55
90
105
120
132
170
690 V
45
55
75
90
105
120
132
170
Capacitators banks switching ability
400 V
[kVar]
60
60
75
90
110
140
160
220
690 V
60
60
75
90
130
130
150
200
Number of poles
3
Screw-type terminals
M8
M10
M12
Rated frquency of operation at category
AC3
[cycles]
5 x105
AC4 5 x104
Rated frquency of operation at category
AC1
[ł/h]
 [c/h]
600150
AC2
AC3 300
AC4 150
Short-time withstand current n-second
10 s
[A]
840
1160
1440
1640
2000
2400
3200
4400
1 s
1500
1700
2000
2500
3000
4000
5500
Slow blow fuse ratings
without tackling / 
at expected current
[A]
160
200
250
250
315
355
500
630
[A]
125
160
160
200
200
250
315
500
[kA]
5
10
10
10
10
10
18
18
Cable cross-section 
with
cable terminal (min/max)
[mm²]
25 / 70
50 / 95
50 / 95
50 / 95
50 / 120
70 / 185
90 / 240
70 / 370
bar type
[mm]
20 x 2
20 x2,5
2(20 x2)
2(25 x2)
2(25 x2)
2(25 x3)
2(25 x4)
2(30 x6)
Electromagnet drive
Rated insulation voltage Ui 
[V]
500
Operating range
 actuating
0,85...1,1 Us
 disactuati
0,75...0,2 Us
Power consumption
 starting
[VA]
770
2200
 holding
44
140
Control voltage (min/max) 
[V]
(50 Hz)
42 / 500
Switching times
 closing
[ms]
15÷20
19÷25
 opening˙
7÷13
8÷12
Auxiliary contacts
Rated insulation voltage Ui
[V]
500
Rated continous current Iu 
[A]
10

Rated switching current Ie category
AC15 - 230 / 400 / 500 V
[A]
6 / 4 / 2
DC13 - 48 / 110 / 220 V
[A]
6 / 1,5 / 0,5
Weight
[kg]
3,9
4 4,2
4,5
9,5
9,6
9,8
10,2

Note!
For the phased out SCM and SC contactors we offer equivalent types as shown in the table below. The new types require relevant adapting elements to be installed.

Old type
Equivalent type
Adopting element
SCM202
SA...M
Reducer SCM / SAM
SC402
SA200
Frame SA200


Dimensions

min C or min. 162 (with double switches) min clearance to metal parts

Type
A
B
C
D
G
SA55M
20
42
138
148
M8
SA75M
20
42
138
148
M8
SA90M
20
42
138
148
M8
SA110M
25
48
144
154
M10


min 180 or 201 (with double switches) min clearance to metal parts

Type
A
B
C
G
SA132
25
48
195
M10
SA160
SA200
SA250
30
53
203
M12



Wiring diagram




Terminals arrangement




Switching diagrams



SA110M/90M/75M Contactors traverese travel 
0  2  4  6  8 10
Main circuits
-
-
Auxiliary circuits
normally
closed (NC)
open (NO) 
special1)
ate break (NC) 
early make (NO)



SA250/200/160/132 Contactors traverese travel 0  3  6  9 12 15
Main circuits
-
-
Auxiliary circuits
normally
closed (NC) 
open (NO)
special1
ate break (NC)
early make (NO)

1) Externals switches only (contacts number from 7 to 12)


Spare parts

Name Identification No Item No.
Coil unit     42V  50Hz B340 1501T02 601-T01-023
Coil unit   110V  50Hz B340 1501T04 601-T01-024
Coil unit   230V  50Hz B340 1501T03 601-T01-025
Coil unit   400V  50Hz B340 1501T05 601-T01-026
Coil unit   500V  50Hz B340 1501T08 601-T01-027
Coil unit   470V  50Hz B340 1501T09 601-T01-030
Coil unit     42V  50Hz B320 1501T02 601-T02-025
Coil unit   110V  50Hz B320 1501T04 601-T02-026
Coil unit   230V  50Hz B320 1501T03 601-T02-027
Coil unit   400V  50Hz B320 1501T05 601-T02-028
Coil unit   500V  50Hz B320 1501T08 601-T02-029
Coil   42V  50Hz B280 1510T01 601-T05-024
Coil   110V  50Hz B280 1511T01 601-T05-025
Coil   230V  50Hz B280 1523T01 601-T05-026
Coil   400V  50Hz B280 1540T01 601-T05-027
Coil   500V  50Hz B280 1550T01 601-T05-028
Switch  "12"  inner B280 1372T01 601-T05-029
Switch  "21"   inner B280 1373T01 601-T05-030
Switch  "11"   left B280 1351T01 601-T05-031
Switch  "11"   right B280 1352T01 601-T05-032
Switch  "12"   left B280 1353T01 601-T05-033
Switch  "12"   right B280 1354T01 601-T05-034
Switch  "21"   left B280 1355T01 601-T05-035
Switch  "21"   right B280 1356T01 601-T05-036
Switch  "12"   outer  left B280 1357T01 601-T05-037
Switch  "12"   outer  right B280 1358T01 601-T05-038
Switch  "21"   outer  left B280 1359T01 601-T05-039
Switch  "21"   outer  right B280 1360T01 601-T05-040
Set of fixed contacts  SA250 B340 1300T01 601-T01-021
Set of moving contacts  SA250 B340 1303T01 601-T01-022
Set of fixed contacts  SA200 B320 1300T01 601-T02-021
Set of moving contacts  SA200 B320 1303T01 601-T02-022
Set of fixed contacts  SA160 B300 1300T01 601-T03-021
Set of moving contacts  SA160 B300 1303T01 601-T03-022
Set of fixed contacts  SA132 B290 1300T01 601-T04-021
Set of moving contacts  SA132 B290 1303T01 601-T04-022
Set of fixed contacts  SA110M B280 1348T01 601-T05-021
Set of moving contacts  SA110M B280 1349T01 601-T05-022
Set of fixed contacts  SA90M B270 1348T01 601-T06-021
Set of moving contacts  SA90M B270 1349T01 601-T06-022
Set of fixed contacts SA75M/SA55M B260 1348T01 601-T07-021
Set of moving contacts SA75M/SA55M B260 1349T01 601-T07-022
Set of deionisation plates SA… B320 1499T01 601-T02-023
Set of deionisation plates SA…M B280 1499T01 601-T05-023




Additional equipment

V-clamps with standard screws

Material: Enclosure: high strength Al-alloy (AlMgSi), corrosion resistant, uncoated. Pressure pad: brass, electro tinned. Screw: brass, electro tinned. Belleville spring: spring steel, galvanized.

Application: connecting single cores of Al and Cu cables, round and sector 90° and 120° types.

Tightening torque: 22+2 Nm.


Type

Cross section
[mm2]

Dimensions
[mm]

Item No.

sm

se

rm

re

b

l

h

V 120

35÷95

50÷120

10÷50

16÷50

27

20

36,5

361-100100

V 300

70÷240

95÷300

50÷185

70÷240

34

22

48

361-100110


Double V-clamps, VD type

Application: Connecting 1÷2 cores of Al and Cu power cables to busbars, terminals of disconnectors, fuse bases etc. The clamps are suitable for all the kinds of cable cores, i.e. sector stranded (sm), sector solid (se), round stranded (rm), round solid (re).

Structure: A complete clamp set consists of VD clamp and PV terminal plate. The appropriate combination can be set by the user.

Type

Cross section
[mm2]

Dimensions
[mm]

Intermediate plate width
[mm]
Weight
[g]

Item No.

sm

se

rm

re

b

l

h

VD 120

35÷95

50÷120

10÷50

16÷50

27

20

54

26,5 79

361-100300

VD 300 120÷240 150÷300 120÷400 120÷400 34 22 74 28,5 152 361-100310


Insulation covers VPI type

Material: polypropylene

Application: as insulation covers for the safety of personnel; they have a hole for Allen wrench.

Type

Types of clamps

Weight
[kg / 100 pcs]

Item No.

VPI-3

V 300, VO 300

2

361-300110


Terminal plates PV type

Material: Cu, electro tinned, thickness 3 mm.

Application: connecting V (VO, VD) clamps to busbars and flat terminals.


Type

Types of clamps

Dimensions
[mm]

Item No.

A

B

s

d

PV 1/8

V 120, VD 120

65

20

3

8,5

361-200100

PV 1/10

65

20

3

10,5

361-200110

PV 2/8

V 300, V 300A, VD 300

72

25

3

8,5

361-200150

PV 2/10

72

25

3

10,5

361-200160

PV 2/12

72

25

3

13

361-200170

PV 3/8

V 300, V 300A, VD 300

72

25

4

8,5

361-200180

PV 3/10

72

25

4

10,5

361-200190

PV 3/12

72

25

4

13

361-200200




Name Identification No Item No.
Contactor locking unit   SA…M / SA…. K100 1102T01 602-T02-011
Reducer SCM/SA110M B280 0100T1 601-T09-001
Frame  SA132 K290 1102T1 601-T09-002
Frame  SA200 K320 1102T1 601-T09-003