SAP sets

Set of the SA contactor with the relay for direct start-up

Construction
SAP set consists of a contactor and a thermal relay sensitive for phase errors, with manual resetting, directly connected to output terminals of the contactor. The thermal relay of 10 A class used in this set is intended for standard start-up times in the range from 2 ÷ 10 s and for start-up currents Ir < 6 x In.

Application
SAP sets are intended mainly for the direct startup and protection of 3-phase electrical motors with rating currents in the range from 60 A up to 400 A, switching voltage up to 690 V / 50 Hz, operating in conditions determined by the usage category AC2 / AC3. These sets should be mounted in enclosures, with current paths running vertically and on supporting structures, which are not subjected to excessive vibrations and shocks. SAP sets fulfill requirements of PN-EN 60947-4-1 standard.



Product range



Set type
Relay adjustment range
Identifcation No
Item No.
-
A
B
-
-
SAP75M
60÷100 A
K262 1
T
0863
604-T06...
75÷125 A
0965
90÷l50 A
0968
SAP90M
75÷125 A
K272 1
T
0965
604-T05...
90÷l50 A
0968
120÷200 A
0973
SAP110M
90÷l50 A
K282 1
T
0968
604-T04...
120÷200 A
0973
SAP132
150÷250 A
K292 0
T
1977
604-T03...
SAP160
150÷250 A
K302 0
T
1977
604-T02...
180÷300 A
1980
SAP200
180÷300 A
K322 0
T
1980
604-T01...
250÷420 A
1990


A - Auxiliary contacts number
| 2 | 2 |
2z+2r
| 2 | 4 |
2z+4r
| 3 | 3 |
3z+3r
| 4 | 2 |
4z+2r

B – Coil voltage (50Hz)
| 4 | 110 V
| 3 | 230 V
| 5 | 400 V
| 8 | 500 V


Ordering example

SAP assembly controlled by 230 V 50 Hz (code 3) voltage with auxiliary contacts 2NO+2NC for starting and protecting against overload squirellcage motors rated 90 kW at 400 V. SAP 90 M (120-200A) 230V 50Hz K272 1223 T 0973



Technical data


Type
SAP75M
SAP90M
SAP110M
SAP132
SAP160
SAP200
Contactor type
-
SA75M
SA90M
SA110M
SA132
SA160
SA200
Relay adjustment range
[A]
60÷ 100
75÷125
90÷150
150÷ 250
150÷ 250
180÷ 300
75÷125
90÷150
90÷150 120÷ 200
120÷ 200
180÷ 300
250÷ 420
Main contacts
Rated insulation voltage
Ui
[V]
1000
Rated power of utilization category AC2/AC3
230 V
[kW]
40
55
55
75
90
110
400 V
75
90
100
132
160
200
500 V
90
110
132
160
200
250
690 V
110
132
132
200
250
315
 Rated control voltage
50 Hz
Us
[V]
42÷500*
Operating range
actuating
-
0,85÷1,1 Us
disactuating
-
0,75÷0,2 Us
Power consumption starting
[VA]
770 220
holding
[VA]
44
140
Switching times
 closing 
[ms]
15÷20
19÷25
opening
[ms]
7÷13
8÷12
Output terminal screw with fat washer
-
M8
M8
M10/M8
M10
M10
M10
Fuse inserts type gG (gL)
-
200
250
250
315
355
500
Max cross-section of cond. 
cond. with cable-type terminal 
[mm²]
95
95
95
120
185
2x120
bus-type conductors
[mm] 
20x2,5
2(20x2)
2(25x2)
2(25x2)
2(25x3)
2(25x4)
Auxiliary contacts
Rated insulation voltage
Ui
[V]
500
Rating thermal current
[A]
10
Rated continous current
AC (230 V)
Iu
[A]
2,5
DC (110 V)
1/1
Number and type of contacts
for contactor
-
*
for relay
-
lz + lr 
Output terminal screw with a fat washer
-
M3,5
Maximum cross-section of conductors 
[mm2]
2,5
Weight
[kg]
8,2
8,4
8,7
12,1
12,2
12,5

* see the specification of assortment.

The other technical parameters of contractors can be found in the relevant catalogue at pages 4 ÷ 9.


Wiring diagram




Dimensions

SAP75M, SAP90M, SAP110M

Type
A
B
C
D
SAP75M/SAP90M
20
42
304
M8
SAP110M
25
48
307
M10




SAP132, SAP160, SAP200