BSA direct starters

Direct start-up devices in metal enclosure

Construction
Direct start-up device type BSA it is a set consisting of the SA contactor and the thermal relay sensitive to overloads with manual resetting. The complete is contained in the metal enclosure protected against corrosion with powder coating in RAL 7032 color. At the bottom and at the top of the enclosure are located cover plates; in these plates are to be drilled holes for sealing glands through which cables of the maincircuit can be led to the inside of the enclosure. In the bottom part of the enclosure are situated the sealing glands of DW13S type for the cables supplying control circuits. Control circuits include pushbuttons START-STOP for ocal control, light signaling indicating the operational status of the start-up device and threaded connectors for connecting the remote control. Used thermal relay of 10 A class is intended for standard start-up times in the range from 2 s up to 10 s and for start-up currents Ir ≤ 6 x In.

Application
Direct start-up devices BSA are intended for the direct start-up and the stoppage of 3-phase motors and for the protection of these motors against effects of working overloads. They enable maneuvering the motors with rating currents in the range from 60 A to 200 A and switching voltage up to 690 V / 50 Hz, operating in conditions determined by usage cate-gory AC2/AC3. Start-up devices are adapted for in-stallation in indoor premises without air-conditioning or for installation under umbrella roof, at the ambient temperatures within the range from - 20 ÷ +40 °C, at temperate climate conditions and at sites located up to 2000 above seal level. Direct starters of BSA type fulfill requirements of PN-EN 60947-4-1 standard.


Product range



Type
Relay adjustment range
Identifcation No
Item No.
BSA75M
60÷100 A
K910 4263
T
1963
605-T06001
75÷125 A
1965
605-T06002
90÷150 A
1968
605-T06003
BSA90M
90÷150 A
K910 4273
T
1968
605-T05001
120÷200 A
1973
605-T05002
BSA110M
90÷150 A
K910 4283
T
1968
605-T04001
120÷200 A
1973
605-T04002
BSA132
150÷250 A
K900 4293
T
1977
605-T03001
BSA160
150÷250 A
K900 4303
T
1977
605-T02001
180÷300 A
1980
605-T02002
BSA200
180÷300 A
K900 4323
T
1980
605-T01001
250÷420 A
1990
605-T01002



Technical data

Type
BSA75M
BSA90M
BSA110M
BSA132
BSA160
BSA200
Relay adjustment range
60÷100
75÷125
90÷150
90÷150
120÷200
90÷150
120÷200
150÷250
150÷250
180÷300
180÷300
250÷420
 Rating current of the starter 
[A]
180
200
220
250
300
400
Max. power of the motor
400V
[kW]
45
55
75
75
90
75
100
110
110
147
147
200
500V
59
80
90
90
110
90
132
160
160
200
200
250
690V
80
100
110
110
132
110
132
200
200
250
250
315
Max. current of the motor 
400V
[A]
85
105
140
140
170
140
188
205
205
273
273
380
500V
85
112
128
128
156
128
186
220
220
278
278
353
690V
86
107
118
118
140
118
140
215
215
268
268
337
Max. rating of gG fuse insert
[A]
160
200
250
250
315
250
315
400
400
500
500
630
Main contacts
Rated insulation voltage
Ui
[V]
1000
 Switching voltage
Us
[V]
400, 500, 690
Continous current
Iu
[A]
acc. to relay range* 
Frequency
[Hz]
50
Switching times 
 closing
[ms] 15÷20 19÷25
opening
[ms] 7÷13 8÷12
Output
Screw with fat washer
- M8 M10/M8 M10
 Busbar N
- M8 M10/M8 M10
Busbar PN
- M8 M10/M8 M10
Max cross-section of cond. 
[mm2]
95
120
185
2x120
Protection degree
-
IP55
Control circuit characteristics
Rated insulation voltage
Ui
[V]
500
 Switching voltage
Us
-
230 V 50 Hz
 Rating thermal current
[A]
10
Power consumption 
 starting
[VA] 770 2200
 holding˙
44 140
Number of type contacts 
 for contactor
- 2z÷2r
for relay
- lz÷lr
Output terminal screw with a fat washer
-
M3,5
 Maximum cross-section of conductors
[mm2]

2,5
Light signaling
-
LEF30-Lec/ NEF30-Lez
Control pushbut
-
LEF30-Kzx/ NEF30-Kcy
Relay properties
-
pushbutton: TEST, tripping indicator
Weight
[kg] 
19
19,5
20
28
29
29

* see the specification of assortment.


Wiring diagram




Ordering example

Direct starter in BSA type housing, with control voltage 230 V 50 Hz is used for the start-up and the overload protection of the squirrel-cage type motor with 200 kW power, at 400 V voltage and classified in usage category AC3
BSA200 (250-420A) K900 4323 T1973



Dimensions



Type
A
B
C
D
BSA75M, BSA90M
42
106
20
M8
BSA110M
48
103
25
M10