LO switch disconnectors

LO-250 and LO-400 switch disconnectors rated up to 400 A

Construction
LO switch disconnectors consist of following main sets:
– the bottom equipped trunk into current (points of junction constants, moving and extinction chambers) tracks,
– the upper (the metal construction) equipped set into the independent (expressed by signs) drive and auxiliary points of junction 2NO +2NC.
Current circuits in main poles possess for two isolating pauses. The hand drive assures the instantaneous joining of points of junction aside from of the speed of the displacement of the lever of the drive. The enclosure and the disconnection of LO switch disconnectors takes place by means the lever of the drive to push with the rotary motion for the corner 90º whose the construction does not permit to qualify current state the switch disconnector. The real position of chattel (the state of the close or the opening) points of junction signalled is only a visible visual indicator from the side of the driving (the green colour ,,O” – the off-state, the red ,, I” – the state of the enclosure)
lever.

Application
LO switch disconnectors are designed for:
– making and breaking the current in alternative current circuits,
– installation inside of enclosed indoor switchgear operated in non-airconditioned compartments. LO can be used in various climate conditions, at the range of ambient temperatures Switch disconnectors fulfil PN-EN 60947-3 standard.
Ambient temperature: 263 ÷ 318 K (-10 ÷ +45 °C)


Product range



Type
Identifcation No
Item No.
LO-250Z
R257 1022 TO
620-T03001
LO-250W
R257 1122 Tl
620-T04001
LO-400Z
R407 1022 TO
620-T01001
LO-400W
R407 1122 Tl
620-T02001


Ordering example
Switch disconnector rated 250 A
LO-250Z R257 1022 TO
Switch disconnector rated 400 A to montage on the plate
LO-400W R402 1122 T1



Technical data

Type
LO-250Z 
LO-250W LO-400Z LO-400W
Main contacts
Rated insulation voltage
Ui
[V]
690
Rated insulation voltage
Ue
[V]
500
Birth-mark percessive tension held out
U imp
[kV]
6
Rated continous current
AC21A, 500 V
Iu
[A]
250
400
Rated switching current
Ie
[A]
30
 Rated current short-circuit 
I cm
-
30
Current od short-circuit duration held out
0,5 s
Iew
[A]
15
Contact life
AC21A, 500 V
[cycles] 
6  000
3  000
Mechanical durability
30  000
10  000
Rated frequency of switching
[h-1]
120
Number of poles
-
3
Usage category˙
-
AC-21A
Protection degree
-
IP00
Threads of terminal screws
cross-section
-
M10
M12
protection
-
M10
M10
Conn. conductors cross-sections
conductors with Terminal
[mm²]
120
240
bus-type conductor
[mm]
30
30
Auxiliary contacts 2z+2r 

Rated insulation voltage
Ui
[V]
400
Rated continous current
Iu
[A]
10
 Rated switching current 

AC15 - 400 V
Ie
[A]
2,5
DC13
[A]
0,16
Max Conn. conductors cross-sections
[mm²]
2,5
Weight
[kg]
3,4 
3,2
3,6


Wiring diagram




Dimensions

P – mounting plate

Type
A
B
LO-250Z
140
162
LO-250W
LO-400Z
154
181
LO-400W